OPERATION AND INSTALLATION GUIDE FOR MODELS: SPS-120 & SPP-180 GILLETTE GENERATORS AUTOMATIC POWER SYSTEMS
PAGE 10 1) Ground Wire to Ground Stake (Electrician) 2) Two Electrical Knockouts (Electrician) 3) Oil fill. 4) Engine. 5) Spark plug (Replace eve
PAGE 11 The control panel is the central point for all automatic controls and wiring points. This panel is made, so that repair person can easily rem
PAGE 12 Propane (LPG) and natural gas (NG) is extremely flammable and explosive. Fire or explosion can cause serious burns or death. LPG
PAGE 13 EXAMPLE 2: A model SPP-180, 16 KW generator is to be installed 50 feet from gas meter. In reading the charts, Fig. 1 shows this
PAGE 14 LPG GAS FUEL This home generator system has been set up at the factory for natural gas fuel, unless it has been specificall
PAGE 15 A flexible LPG fuel line is furnished for installation between the LPG fuel line & generator fuel input. CAUTION: Make sure thi
PAGE 16 Electrician must remove (3) cap screws (see arrows) and slide panel down 2 inches, then pull straight out for complete removal.
PAGE 17 Dielectric grease should be used on battery lugs or posts to help in the prevention of normal corrosion. Damage will result to ge
PAGE 18 NOTE: For air temperatures below 32º F (0º C), it is highly recommended to replace oil with a synthetic oil, API SJ/CF 5W-30W.
PAGE 19 NGLPMODEL SPS-120 use the gas system as shown above. The KN gas regulator is used to regulate the gas flow by responding to pressure change
PAGE 2 TABLE OF CONTENTS Page Introduction, General Cautions, Warnings, & Danger Points ------------------ 3-6 Un-
PAGE 20 BE EXTREMELY CAREFUL. YOU ARE READY TO TEST RUN A GENERATOR THAT HAS BOTH ELECTRIC SHOCK AND FLAMMABLE FUEL POTENTIAL HAZARDS.
PAGE 21 voltage and frequency at no load conditions. Typical no load test readings should be 230-245 volts at 61.0-61.5 hertz. After all meter tes
PAGE 22 dipstick and oil fill cap to facilitate complete draining process. When oil is drained, replace dip stick, oil fill cap, oil hose drain cap
PAGE 23 BASIC SERVICE TIPS/TROUBLE SHOOTING GUIDE BASIC SERVICE TIPS, TROUBLE SHOOTING AND NEW START-UP HELP, FOR YOUR GILLETTE STANDBY GENERATOR: A)
PAGE 24 DRAWING NOT TO SCALE & DIMENSIONS = IN [MM](A) (4) LIFTING HOLES IN BASE:1-1/2" DIA. HOLES ARE INSTALLED IN BASE, FORLIFTING EQUIPME
PAGE 25 ENGINE ENDPANELS REMOVEDFOR MOUNTINGBOLT VIEWMOUNTING DIMENSIONS FOR 3600 RPM SPS SERIES STANDBY SETS 12 KWCOOLING AIRINTO ENGINEMOUNTING PAD
PAGE 26 ENGINE END VIEWGENERATOR END VIEWSIDE VIEWTOP VIEWSENTRY−PRO DIMENSIONAL OVERVIEW PRINT MODEL SPP−180DRAWING NOT TO SCALE & DIMENSIONS =
PAGE 27 MOUNTING DIMENSIONS FOR 3600 RPM SPP SERIES STANDBY SETS 18 KWEXHAUST AIRFROM RADIATORAND MUFFLERMOUNTING PAD SHOULDBE SET ON A 3" HIGHBE
PAGE 28 OVER CRANKLOW OILNOT IN STANDBYLOW BATTERYUNDER SPEED / FAILENGINE RUNNINGOVER SPEEDENGINE MONITOROFF / RESETTESTSTANDBYMODE SELECTORby GILLE
PAGE 29 OVER CRANKLOW OILNOT IN STANDBYLOW BATTERYUNDER SPEED / FAILENGINE RUNNINGOVER SPEEDENGINE MONITOROFF / RESETTESTSTANDBYMODE SELECTORby GILLET
PAGE 3 THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS THAT MUST BE FOLLOWED DURING INSTALLATION, OPERATION, AND MAINTENANCE OF THIS GENERATO
PAGE 30 SERVICE SCHEDULE SYSTEM COMPONENT OR PROCEDURE SEE PAGE CHECK CHANGE CLEAN TEST FREQUENCY ENGINE AIR CLEANER X X R YEARLY OR EV
PAGE 31 MAINTENANCE RECORD Use the following table to keep a record of all periodic and unscheduled maintenance and service. See Se
GILLETTE GENERATORS AUTOMATIC POWER SYSTEMS OGU08-OWN-798-20121029 Gillette Generators, Inc. 1340 Wade Drive Elkhart, IN 46514 Phone: 574-264-9639 Fax
PAGE 4 NOTICE ● For all safety reasons to the equipment, GILLETTE recommends installation, start-up and service be performed by experienced
PAGE 5 ELECTRICAL HAZARDS A generator produces dangerous electric voltages and can cause a fatal electric shock and will cause sudden
PAGE 6 FIRE OR EXPLOSION CONDITIONS Gaseous fuels such as natural gas (NG) and liquid propane (LP) are extremely explosive. Make sure the
PAGE 7 GENERATOR CONTENTS The GILLETTE home generator set is supplied with the following components: ● Home generator system within sou
PAGE 8 3) PREFERRED: Generator is mounted directly on a concrete slab, 4 inches thick, extending 6 inches beyond generator perimeter, and
PAGE 9 (1) Drawing shows a typical gas utility approach on how to bring natural gas fuel to the gen-set. The fuel from utility